Maximum number of verification intervals: nLC = 6000
Sensitivity: 2mV/V ± 10%
Temperature effect on zero:
7kg: ±0,0084% F.S./10K
10kg: ±0,0070% F.S./10K
18kg: ±0,0070% F.S./10K
36kg: ±0,0070% F.S./10K
Temperature effect on Full Span:
range -10°C/+20°C: 0,0058% F.S./10K
range +20°C/+40°C: 0,0087% F.S./10K
Compensated Temperature Range: -10°C/+40°C
Operating Temperature Range: -10°C/+50°C
Maximum excitation voltage without damage: 15 Vdc
Input Resistance: 300..500 Ohm
Output Resistance: 300..500 Ohm
Zero Balance: 0 ±0,1mV/V (at 100V)
Insulation Resistance: >2000 MOhm
Mechanical limit load in service: 150% F.S.
Destructive load: 300% F.S.
Deflection at nominal load <0,5mm
6-wire shielded cable, 3m long, 4,7mm diameter
The CCATEX certificate makes the load cell suitable for use in hazardous areas with protection methods according to:
ATEX II 1G Ex ia IIC T6 (Ta -20÷+40°C) TX (Ta -20÷+65°C) Ga
ATEX II 1D Ex ta IIIC TX°C (Ta -20÷+40°C) TX°C (Ta -20÷+65°C) Da IP65.
The certificate includes the manual and the ATEX CE conformity declaration (available in EN, DE, FR, and IT).
IMPORTANT: the certificate refers to the single load cell. For systems with more load cells, it is necessary to order one certificate for each load cell.