Starting at £0.00 £0.00
Minimum load cell verification interval:
Vmin = EMax / 7.500-12.500
Maximum number of verification intervals: nLC = 3000
Full Scale Output: 2mV/V +/- 10%
Temperature effect on zero:
from ±0,0112% F.S./10K to ±0,0186% F.S/10K
Temperature effect on full scale output:
±0,0117% F.S./10K (-10°C/+20°C)
±0,0170% F.S./10K (+20°C/+40°C)
Compensated Temperature Range: -10°C/+40°C
Operating Temperature Range: -10°C/+50°C
Creep at nominal load in 30 minutes: ± 0,01% F.S.
Maximum tolerated excitation voltage: 15 VDC
Input Resistance: 380 ± 15 Ohm
Output Resistance: 300...500 Ohm
Insulation Resistance (100V) >2000 MOhm
Safe Overload: 150 % F.S.
Ultimate Overload: 300% F.S.
Nominal displacement: < 0.5 mm
6-wire shielded cable, 3m long, 5mm diameter
| Cable Length | 3m |
|---|---|
| IP Rating | IP69K |